Fouling Energy Penalty Rule

Field rule estimating extra chiller energy from fouling: each 1 degree F rise in condenser approach raises chiller energy consumption by about 1.5 to 2 percent. Translates fouling into operating cost.

Variables

SymbolMeaningUnit
\Delta P_%Percent increase in chiller energy consumptionpercent
Rise in condenser approach temperaturedegrees F

Worked example

A 1,000-ton chiller at 0.60 kW/ton draws 600 kW. Baseline at 4,000 hr/yr and 240,000/yr. A 5 degree F approach rise at 2 percent per degree adds 600 x (5 x 0.02) = 60 kW, so 660 kW gives 24,000 more per year.


Part of The Blueprint of Water