Problem 3.8: A field report lists conductivity as 23 mScm A
From Chapter 3 Problem Set. Level 3: System Integration.
Question
A field report lists conductivity as “2.3 mS/cm.” A technician enters it into a spreadsheet as 2.3 µS/cm. By what factor is the TDS estimate wrong, and what operational consequence could this cause?
Answer
Show answer
The error is a factor of 1,000 (1 mS/cm = 1,000 µS/cm). The technician’s TDS estimate would be 1,000 times too low. This could lead to severe under-blowdown - the system would concentrate far beyond safe limits while the spreadsheet shows acceptable chemistry.