Problem 11.1: A cooling tower suddenly shows higher
From Chapter 11 Problem Set. Level 1: Conceptual Mastery.
Question
A cooling tower suddenly shows higher conductivity, higher pH, and weaker oxidant residual. Before adjusting any feed pump, list:
- what may have changed in what enters?
- what may have changed in what leaves?
- what may now be accumulating?
- and what transformations may be occurring faster than before?
Answer
Show answer
Likely possibilities include:
- What enters: Makeup fraction may have increased, incoming solids may have increased, contamination may have entered, or inlet temperature may have changed.
- What leaves: Blowdown may have decreased, a valve may have failed, filtration may have lost effectiveness, or another removal pathway may have changed.
- What accumulates: Dissolved solids, deposits, biomass, and sludge may now be accumulating.
- What changes form: Bicarbonate may be shifting toward carbonate at higher pH, oxidant demand may be increasing through reaction with organics or biofilm, and dissolved species may be precipitating as solids.