Problem 11.9: A condenser system shows inhibitor residual on
From Chapter 11 Problem Set. Level 3: System Integration.
Question
A condenser system shows:
- inhibitor residual on target
- pH in range
- conductivity in range
- biocide schedule maintained
- no visible heavy scale
But corrosion coupons show 6.5 MPY.
Explain at least two ways this can happen using the distinction between bulk-water chemistry and surface conditions.
Answer
Show answer
Two strong explanations are:
- Under-deposit corrosion: Bulk chemistry may be acceptable, but deposits isolate the metal beneath them from inhibitor protection and create local oxygen differentials.
- MIC or localized biofilm attack: The water column may test well while the surface microenvironment remains biologically active and corrosive.
Other acceptable explanations include:
- flow-related erosion-corrosion
- galvanic effects
- poor coupon location
- coupon exposure that reflects a particularly aggressive part of the system rather than the average system condition
The key idea is that bulk water data does not guarantee surface protection.