Problem 12.7: An 800ton chiller operates at 060 kWton under

From Chapter 12 Problem Set. Level 2: Applied Thinking.

Question

An 800-ton chiller operates at 0.60 kW/ton under clean conditions for 4,500 hours per year at $0.11/kWh. Condenser tube fouling has increased the approach temperature by 4°F. Using the upper-end estimate (2% energy increase per °F of approach rise), calculate:

Answer